Appendix VI Pipe And Conduit Identification Standards
Identify all accessible pipe and conduit by stenciled letters or pipe markers. Locate so identification is visible from expected personnel approach. Space at 30' maximum with at least one in each room and one directly adjacent to each main, sectionalizing or isolating valve. Color shall be black.

Lettering Size For Pipe And Conduit Identification
O.D. of Pipe or Insulation Height of Lettering
2" and smaller .5
Over 2" 1"


Mandatory Symbols For Pipe And Conduit Identification
F Automatic Fire Sprinkler
LV Laboratory Vent
LW Laboratory Waste
ChWR Chilled Water Return
ChWS Chilled Water Supply
Com Communications Conduit
CA--- Compressed Air (with Pressure)
CR Condensat Return
DI Deionized Water
DW Distilled Water
DCW Domestic Cold Water
DHW Domestic Hot Water
DHWR Domestic Hot Water Return
DSP Dry Standpipe
E Electric Conduit
FA Fire Alarm Conduit
G Natural Gas (with pressure if above 8" W.C.)
HHW Heating Hot Water
HHWR Heating Hot Water Return
HPS High Pressure Steam (41 psi and over)
ICW Industrial Cold Water
IHW Industrial Hot Water
IHWR Industrial Hot Water Return
LPS Low Pressure Steam (up to 15 psi)
MPS Medium Pressure Steam (16 to 40 psi)
OX Oxygen
RWL Rain Water Leaders (including drains)
HG Refrigerant Hot Gas
RL Refrigerant Liquid
RS Refrigerant Suction
SS Sanitary Sewer
V Sanitary Vent
Tel Telephone Conduit
TWR Tower Cooling Water Return
TWS Tower Cooling Water Supply
VAC Vaccum Laboratory
WSP Wet Standpipe System