Capital Projects Home Page

Fire and Life Safety - 03 - Fire Flow Requirements for Buildings
  1. This procedure shall be used for determining fireflow requirements for all buildings or portions of buildings hereafter constructed. This section is not intended to apply to structures other than buildings.


  2. The fireflow requirement is the quantity of water in gallons per minute, measured at 20 psi residual pressure, that is available for fire fighting.


  3. Fire area is the total floor area in square feet for all floor levels within the exterior walls, or under the horizontal projection of the roof of a building. Each portion of a building separated by one or more four-hour area separation walls with no openings and provided with a 30" parapet constructed in accordance with the Building Code may be considered as separate fire areas for the purposes of determining the required fire flow.


  4. The fire flow shall be not less than that specified in Table 1-03-A. Exception: Fire flow may be reduced up to 75% when the building is provided with an approved automatic sprinkler system throughout, but in no case less than 1500 gallons per minute.


  5. In types I and II F. R. Construction, only the three largest successive floor areas shall be used.


  6. When design begins for any new construction that is to be supplied from the campus water distribution system, the Campus Fire Marshal and Physical Plant-Campus Services (PP-CS) both need to be notified by the project manager. They will review water needs of the project to determine the best possible point of connection to the system, and to specify the appropriate fire hydrant flow test(s) to confirm the available flow.


  7. Hydrant flow tests shall be conducted using the methods outlined in NFPA Standard #291.

    All fire hydrant flow tests are to be performed by a licensed Fire Protection Engineer or other qualified consultant and are to be paid for by the project manager. It is recommended that PP-CS and UCFPD be present at all fire hydrant flow tests. For off-campus sites, UCFPD will coordinate with the Berkeley Fire Department for fire hydrant flow data and/or tests.

Return to Fire and Life Safety Table of Contents